Laserfiche WebLink
APPENDIX H <br />494 2015 MINNESOTA STATE FIRE CODE <br />FIGURE 4 <br />SECTION II—HAZARDOUS MATERIALS INVENTORY STATEMENT (HMIS) HMIS SUMMARY REPORTa (Storageb Conditions)c <br />a. Complete a summary report for each control area and Group H occupancy. <br />b. Storage = storage + use-closed + use-open systems. <br />c. Separate reports are required for use-closed and use-open systems. <br />d. Include increases for sprinklefrs or storage in cabinets, if applicable. <br />(This is an example; add additional hazard classes as needed.) <br />IBC/IFC HAZARD CLASS HAZARD CLASS INVENTORY AMOUNT IBC/IFC MAXIMUM ALLOWABLE QUANTITYd <br /> (Abbrev) Solid (lb) Liquid (gal) Gas (cu ft, gal, lb) Solid (lb) Liquid (gal) Gas (cu ft, gal lb) <br />Combustible <br />Liquid C2 5 120 <br /> C3A 330 <br /> C3B 6 13,200 <br /> <br />Combustible Fiber Loose/Baled <br />Cryogenics, Flammable Cryo-Flam 45 <br />Cryogenic, Oxidizing Cryo-OX 45 <br /> <br />Flammable Gas FLG <br />(Gaseous) 150 1,000 <br />(Liquefied) 30 <br /> <br />Flammable Liquid F1A 30 <br /> F1B & F1C 5 120 <br />Combination (1A, 1B, 1C) 5 120 <br /> <br />Flammable Solid FLS 125 <br /> <br />Organic Peroxide OPU 0 <br /> OP1 5 <br /> OP2 50 <br /> OP3 125 <br /> OP4 NL <br /> OP5 NL <br /> <br />Oxidizer OX4 0 <br /> OX3 10 <br /> OX2 250 <br /> OX1 4,000 <br />Copyright © 2016 ICC. ALL RIGHTS RESERVED. Accessed by James Lee on Dec 14, 2016 8:21:27 AM pursuant to License Agreement with ICC. No further reproduction or <br />distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE <br />AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.