T%3 <br />3802 UNIFORM BUILDING CODE <br />installed in Group A Occupancies which have more than 12.000 square feet of <br />floor area which can be used for exhibition or display purposes. <br />4. Stairs. An automatic sprinkler system shall be installed in enclosed usable <br />space below or over a stairway in Group A, Divisions 2, 2.1, 3 and 4 Occupan- <br />cies. See Section 3309 (f). <br />5. Other areas. An automatic sprinkler system shall be installed under the roof <br />and gridiron, in the tie and fly galleries and in all places behind the proscenium <br />? wall of st ages; over and within permanent platforms in excess of 500 square feet in <br />area; and in dressing rooms, workshops and storerooms accessory to such stages <br />;, or permanent platforms. <br />EXCEPTIONS: I . Stages or platforms open to the auditorium room on three or <br />more sides. <br />2. Altars, pulpits or similar platforms and their accessory rooms. <br />3. Stage gridirons when side -wall sprinklers with 135 °F. rated heads with heat- <br />baffle plates are installed around the entire perimeter of the stage except for the <br />proscenium opening at points not more than 30 inches below the gridiron nor more <br />than 6 inches below the baffle plate. <br />4. Under stage or under platform areas less than 4 feet in clear height used <br />exclusively for chair or table storage and lined on the inside with materials approved <br />for one -hour fire - resistive construction. <br />(d) Group B, Division 2 Occupancies. Art automatic sprinkler system shall be <br />installed in retail sales rooms classed as Group B. Division 2 Occupancies where <br />the floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all <br />floors or in Group B. Division 2 retail sales occupancies more than three stories in <br />height. The area of mezzanines shall be included in determining the areas where <br />.4 sprinklers are required. <br />(e) Group E Occupancies. I . Basements. An automatic sprinkler system shall <br />be installed in basements classified as a Group E Occupancy when the basement is <br />larger than 1500 square feet in floor area. <br />2. Stairs. An automatic sprinkler system shall be installed in enclosed usable <br />space below or over a stairway in Group E Occupancies. See Section 3309 (f). <br />(f) Group H Occupancies. I. Division 1. An automatic fire- extinguishing <br />system shall be installed in Group H, Division 1 Occupancies larger than 1500 <br />square feet in floor area. <br />2. Division 2. An automatic fire - extinguishing system shall be installed in <br />Group H, Division 2 Occupancies exceeding 1500 square feet in area. <br />An automatic fire - extinguishing system shall be installed in rooms of Group H, <br />Division 2 Occupancies when flammable or combustible liquids are stored or <br />handled in excess of the quantities set forth in Table No. 9 -A, or any combination <br />of flammable liquids exceeds 240 gallons. <br />An automatic fire - extinguishing system shall be installed in paint spray booths <br />or rooms. <br />3. Division 3. An automatic fire - extinguishing system shall be installed in <br />Group H, Division 3 Occupancies larger than 3000 square feet in floor area. <br />598 <br />Page 9 <br />