Laserfiche WebLink
Lino Lakes, MN Water Storage Analysis <br />Water Use Projections & Storage Requirement <br />Calculation <br />----|- <br />Design Year 2020 2030 2040 |Equation <br />With 3 Hour Fire With 3 Hour Fire With 3 Hour Fire <br />----|- <br />| <br />Estimated Population 18,250 24,900 29,900 |A <br />Per Capita Water Use (gpd/capita)100 100 100 |B <br />Average Day Water Use (gpd)1,825,000 2,490,000 2,990,000 |C= A*B <br />| <br />Max/Avg Day Ratio 3.57 3.57 3.57 |D <br />Maximum Day Water Use (gpd)6,515,000 8,889,000 10,674,000 |E= C*D <br />Maximum Day Water Use (gpm)5430 7410 8900 |F= E»time <br />| <br />Firm Pumping Firm Capacity (gpm) -Pumps to System 4345 6345 8345 |G <br />5214000 7614000 10014000 | <br />Design Fire Fighting Rate (gpm)3500 3500 3500 |H <br />Fire Fighting Duration (hour)3 3 3 |I <br />Design Fire Fighting Volume (gal)630,000 630,000 630,000 |= H*I*60 <br />| <br />TOTAL Coincident Demand (gpm)8,930 10,910 12,400 |J= F+H <br />Required Draft From Storage (gpm)4,585 4,565 4,055 |K= J-G <br />| <br />Adjusted Fire Fighting Storage (gallons)825,000 822,000 730,000 |L= K*I*60 <br />Equalization Storage (gallons)1,628,750 2,222,250 2,668,500 |M= E*equl <br />TOTAL Storage Need (gallons)2,453,750 3,044,250 3,398,500 |N= L+M <br />| <br />Existing Elevated Storage (gallons)2,000,000 2,000,000 2,000,000 |P <br />| <br />Additional Storage Need (gallons)453,750 1,044,250 1,398,500 |Q= N-P <br />| <br />----| <br />| <br />| <br />Assumptions:| <br />-| <br />Time to Supply Max Day | <br />20 |time <br />Equalization Storage | <br />25%|equal