Laserfiche WebLink
Centennial Fire District 12/18/2002 <br />1306 Comparison <br />A -4 Assembly uses intended for viewing of indoor sporting events .and <br />activities with spectator seating. <br />2000 Building Code — Sprinkle when over 12,000 sq. ft: or <br />more than 300 occupants. <br />New 1306 — Sprinkle all: <br />A -5 Assembly uses intended for participation in or viewing outdoor <br />activities. <br />2000 Building Code — Sprinkle concession stands, retail sales <br />areas, press boxes when they are over 1,000 sq. ft. <br />Business Group B. Business Group B occupancy includes, among others, <br />use of a building or structure, or a portion thereof, for office, professional or <br />service -type transactions, including storage of records and accounts. <br />2000 Building Code - None <br />Old 1306 — Sprinkle when over 8,500 sq. ft. or 3 or more <br />stories. <br />New 1306 — Sprinkle when over 2,000 sq. ft. <br />Educational Group E. Educational Group E occupancy includes, among <br />others, the use of a building or structure, or a portion thereof, by six or more <br />persons at any one time for educational purposes through the 12th grade. <br />2000 Building Code — Sprinkle when over 20,000 sq. ft and <br />every level below level of exit discharge. <br />Old 1306 Sprinkle when over 8,500 sq. ft. or 2 or more <br />stories. <br />New 1306 — Sprinkle when over 2,000 sq. ft. <br />Day care. The use of a building or structure, or portion thereof, for <br />educational, supervision or personal care services for more than five children <br />older than 21/2 years of age, shall be classified as a Group E occupancy. <br />Page 2 of 8 <br />