Laserfiche WebLink
Centennial Fire District <br />1306 Comparison <br />Storage Group S. Storage Group S occupancy includes among others, the <br />use of a building or structure, or a portion thereof, for storage that is not <br />classified as a hazardous occupancy. <br />12/18/2002 <br />S -1 Buildings occupied for storage uses, which are not classified as Group <br />S -2. <br />2000 Building Code — Sprinkle when over 12,000 sq. ft. <br />Old 1306 - Sprinkle when over 5,000 sq. ft. <br />New 1306 — Sprinkle when over 2,000 sq. ft. <br />S -2 . Includes, among others, buildings used for the storage of <br />noncombustible materials such as products on wood pallets or in <br />paper cartons with or without single thickness divisions; or in paper <br />trim such as knobs, handles or film wrapping. <br />2000 Building Code — Sprinkle when over 5,000 sq. ft. <br />Old 1306 — Sprinkle when over 5,00Q sq. ft. <br />New.1306 — Sprinkle when over 5,000 sq. ft. <br />Page 8 of 8 <br />