8 <br />3.3 Cathodic Protection System (C. P.) <br />3.3.1 There are remnants of a submerged C. P. system which at some point has <br />been removed. See photo 21. While most of the components have been <br />removed, some remain and should be removed in conjunction with the <br />next reconditioning. While C. P. is considered an inexpensive form of <br />interior corrosion protection, it is not be required if the coating is applied <br />and maintained properly. <br />3.4 Interior Dry Structural <br />3.4.1 Remove and replace the inoperable pipe -style ladder safety climb device <br />on the ladder in the drywell tube with a new OSHA compliant cable - <br />style ladder safety climb device, which accept more universally available <br />grabs. See photos 25 through 27 and KLM Drawing No. 21. Similarly, <br />install a cable -style ladder safety climb device on the ladder to the bowl <br />manway. See photo 33. The owner may wish to consider installing <br />safety climb devices on each of the other ladders in the pedestal as well, <br />although this is not included in the Engineer's Cost Estimate. <br />3.4.2 Install ports in the center of the drywell tube floor and the condensate <br />ceiling, to facilitate containment during the next reconditioning. See <br />photos 28, 29 and 36 and KLM Drawing No. 52. <br />3.4.3 Install a new 24 -inch diameter, pressure style manway in the upper bowl. <br />This will improve the ventilation during reconditioning and bring the <br />tank into compliance with OSHA Confined Space Entry requirements. <br />This manway should include a ladder from the top platform to the bowl <br />for safe access. See KLM Drawing No. 26. <br />3.4.4 Additional structural items are included in Section 3.9, <br />Telecommunications Considerations, as they relate to the <br />telecommunications installations on the tower. <br />3.5 Interior Dry Coating <br />3.5.1 The tower was built and the interior dry area was last coated in 1992. <br />The interior dry coating is in good to excellent condition, with coating <br />failures limited to areas susceptible to condensation or standing water, <br />such as the drywell tube, bowl, the platform floors, and the piping in the <br />valve pit. These areas should be repaired in conjunction with interior <br />wet coating replacement. The remainder of the coating is in excellent <br />condition and requires no repairs. See photos 25 through 40. <br />