CITY OF LINO LAKES
RESOLUTION NO. 20-50
A RESOLUTION APPROVING AIR DUCT AND DIFFUSER
CLEANING AT CIVIC COMPLEX CONTRACT
WHEREAS, As a result of concerns brought forth from some employees within the Public
Safety Department, Industrial Hygiene Services Corporation (IHES) was retained to conduct
indoor air quality and fungal sampling at the Police Department;
WHEREAS, The sampling occurred on April 28, 2020. The results of the fungal spore samples
showed that there is not an indoor fungal air quality problem. All the indoor air quality
parameters were also within all regulations and recommendations. The only abnormal results
were the fungal tease tape sample collected from the supply diffuser;
WHEREAS, IHES recommends that all supply diffusers within the Civic Complex be cleaned;
WHEREAS, In addition, we are recommending all supply and return air ducts in the Police
Department be cleaned;
WHEREAS, NAC Mechanical has obtained two quotes to clean all diffusers in the Civic
Complex, and clean the supply and return air ducts at the Police Department;
WHEREAS, Staff recommends accepting the NAC proposal that includes subcontracting with
KMS Air Duct Cleaning in the amount of $11,065.00;
WHEREAS, Funding will be from the General Fund Operating Contingency.
NOW, THEREFORE BE IT RESOLVED by The City Council of The City of Lino Lakes
hereby approves the air duct and diffuser cleaning at civic complex contract in the amount of
$11,065.00.
Adopted by the Council of the City of Lino Lakes this 26th day of May, 2020.
The motion for the adoption of the foregoing resolution was introduced by Council Member
Stoesz and was duly seconded.by Council Member Ruhland and upon vote being taken thereon,
the following voted in favor thereof:
Stoesz, Ruhland, Cavegn, Lyden, Rafferty
The following voted against same:
none Ro. ' afferty, Mayor
ATTEST:
id[i 1 Bartell City rk
CITY COUNCIL
AGENDA ITEM 5A
STAFF ORIGINATOR: Rick DeGardner, Public Services Director
MEETING DATE: May 26, 2020
TOPIC: Consider Resolution 20-50, Approving Air Duct and Diffuser
Cleaning at Civic Complex Contract
VOTE REQUIRED: 3/5
INTRODUCTION
The City Council is being requested to authorize the cleaning of the air duct work at the Police
Department and all diffusers at the Civic Complex (Police Department, City Hall, New
Creations).
BACKGROUND
As a result of concerns brought forth from some employees within the Public Safety
Department, Industrial Hygiene Services Corporation (IHES) was retained to conduct indoor
air quality and fungal sampling at the Police Department. The sampling occurred on April 28,
2020. The results of the fungal spore samples showed that there is not an indoor fungal air
quality problem. All the indoor air quality parameters were also within all regulations and
recommendations. The only abnormal results were the fungal tease tape sample collected from
the supply diffuser (report attached).
IHES recommends that all supply diffusers within the Civic Complex be cleaned. In addition,
we are recommending all supply and return air ducts in the Police Department be cleaned. With
the Civic Complex being in operation since 1999, it makes sense to clean the duct work at the
same time the diffusers are being cleaned. Based on the results of the duct cleaning in the
Police Department, we will be able to ascertain the level of urgency of cleaning the remaining
duct work in the Civic Complex.
NAC Mechanical installed the original HVAC system and has been the City's HVAC
contractor ever since. NAC Mechanical has obtained two quotes to clean all diffusers in the
Civic Complex, and clean the supply and return air ducts at the Police Department.
Staff recommends accepting the NAC proposal that includes subcontracting with KMS Air
Duct Cleaning in the amount of $11,065.00 (see attached). Funding will be from the General
Fund Operating Contingency.
RECOMMENDATION
Approve Resolution 20-50.
ATTACHMENTS
Resolution 20-50
IHES Report, dated May 6, 2020
NAC Proposal, dated May 19, 2020
•
•
•
•
INDUSTRIAL HYGIENEHE SERVICES CORPORATION
May 6, 2020
Mr. Rick DeGardner
640 Town Center Parkway
Lino Lakes, MN 55014
Subject: Indoor Air Quality and Fungal Sampling Results
Lino Lakes Police Department
Lino Lakes, Minnesota
IHSC Project Number: M20-694
Dear Mr. DeGardner:
Industrial Hygiene Services Corporation (IHSC) conducted indoor air quality and fungal
sampling at the Lino Lakes Police Department at 640 Town Center Parkway in Lino Lakes,
Minnesota. Sampling occurred on April 28, 2020. Sampling and analysis were conducted
in response to a black residue coming from the air handling unit diffusers and the possible
presence of mold. The black dust/residue was released when the heating, ventilation and
air conditioning (HVAC) system was having maintenance conducted and the air flow was
set much higher than normal running conditions.
MOLD ASSESSMENT CRITERIA
The technical approach used for this evaluation followed standard mold evaluation
protocols for the parameters included in the scope of work. The protocols and assessment
criteria used to conduct the survey were based on those established by the National
Institutes of Occupational Safety and Health, American Industrial Hygiene Association
(AIHA), the American Conference of Governmental Industrial Hygienists, the New York City
Department of Health "Guidelines on Assessment and Remediation of Fungi in Indoor
Environments," Environmental Protection Agency's "Mold Remediation in Schools and
Commercial Buildings," and industry practices.
In each of these referenced guidance documents, a visual inspection is the most important
initial step in identifying a possible contamination problem. Industrial Hygiene Services
Corporation relied upon this approach in conducting an inspection of viewable and readily
accessible room surfaces in conjunction with air sampling and surface sampling.
Mr. Rick DeGardner
Lino Lake Police Department
Indoor Air Quality and Fungai Sampling Results
IHSC Project Number: M20-694
May 6, 2020
Page 2 of 7
There is consensus that visible mold growth should be considered unacceptable in the built
environment from the perspectives of known and potential adverse health effects and
building performance. If visible mold is found, then it needs to be removed under controlled
conditions, as stated in the above -referenced guidance documents.
In assessing the potential for microbial exposures through sampling, it is important to note
that individual microbial measurements provide a limited view of conditions since levels can
fluctuate widely over time and under varying environmental conditions. Therefore, sample
results in this report pertain only to conditions present at the time the samples were
collected and may not reflect other time periods or conditions.
SAMPLING PROCEDURE
Industrial Hygiene Services Corporation conducted fungal spore trap sampling and tease
tape sampling at the above referenced facility. Fungal spore trap sampling occurred in
locker room and the Deputy Director's office. Fungal tease tape sample was collected from
the supply diffuser in the work out room. A reference fungal spore trap sample was also
obtained from the exterior of the building. Industrial Hygiene Services Corporation also
measured common indoor air quality parameters in the locker room and Deputy Director's
office.
Viable and Non -viable Spore Trap Samples
To characterize the ambient airborne condition of viable and non -viable fungal spores in the
area of concern, a calibrated pump was used to draw 150 liters of air through a 37-
millimeter cassette (Allergenco-D) that contains an adhesive faced material collection
surface. Samples were submitted to EMSL Analytical, Inc. (EMSL) for analysis. EMSL is
certified by AIHA for the analysis performed. The concentration and type of airborne spores
in the air were determined using analytical method American Society for Testing and
Materials D7391.
Fungal Tease Tape Sample
To identify the black dust residue on the diffusers throughout the facility. Industrial Hygiene
Services Corporation collected one fungal tease tape sample.
American Society of Heating, Refrigerating and Air Conditioning Engineers
(ASHRAE) Common Indoor Air Quality Parameters
Industrial Hygiene Services Corporation setup a TSI IAQ Calc in the locker room and
Deputy Director's office. The instrument recorded the carbon monoxide, carbon dioxide,
temperature and humidity levels throughout the ten-minute sampling time.
•
Mr. Rick DeGardner
Lino Lake Police Department
Indoor Air Quality and Fungal Sampling Results
IHSC Project Number: M20-694
May 6, 2020
Page 3 of 7
OBSERVATIONS & TEST RESULTS
Observations
Regarding site conditions, no musty or moldy odor, no visible water damage or suspect
mold growth was observed in the areas sampled. Industrial Hygiene Services Corporation
did notice that on the supply diffusers there was a black dust/residue. The observations of
the conditions are indicated below.
• No suspect odors or visible mold growth.
• No visible water damages.
• Black dust/residue was found on the supply diffusers.
Viable and Non -Viable Spore Trap Sample Results
The sample locations and quantitative results for samples collected on April 28, 2020, are
as follows:
Sample
Number
Sample
Location
Total
Volume
Collected
(Liters)
Spores
per
Cubic
Meter
of Air
Organisms
Identified
Percentage
of
Organisms
in the
Sample
01M
Locker
Room
150
20
7
Ascospores
Cladosporium
74.1
25.9
02M
Deputy
Director's
Office
150
30
Cladosporium
100
03M
Exterior
Front
Entrance
150
20
3140
240
640
70
Alfernaria
Ascospores
Aspergillus/Penicillium
Basidiospores
Cladosporium
0.5
76.4
5.8
15.6
1.7
No strict numerical guidelines for assessing indoor fungal contamination have been
determined or published by state or federal regulatory agencies, but guidelines have been
developed by scientific and regulatory communities to aid in the evaluation of analytical
results.
•
Mr. Rick DeGardner
Lino Lake Police Department
Indoor Air Quality and Fungal Sampling Results
IHSC Project Number: M20-694
May 6, 2020
Page 4 of 7
In a properly operating air conveyance system, the indoor concentration of airborne fungal
spores should be approximately the same or less than the concentration of airborne spores
detected outside of the building.
Time of year plays a significant role in determining fungal species present and relative
indoor and outdoor airborne fungal concentrations. Activities within the building will also
influence conditions that may support fungal growth that is unique to the outside of the
building. In general, the following criteria can be used to make a determination that
conditions exist on the interior of the building that are unique and may require further
investigation:
1. Predominate (upper 90% of total) fungi present indoors are not detected outdoors.
2. The predominate genera found indoors is different than the genera found
outdoors.
3. Unusual evidence of fungal growth or water staining of building material is noted in
the area where samples are collected.
4. Comparison of data obtained from the same areas within a similar timeframe
reveal significantly divergent results.
The laboratory results of the mold air samples showed that the indoor sample total mold
concentrations were much lower in the sample areas in comparison with the level
measured on the exterior of the building. The rank order and diversity of mold in the indoor
samples were similar to the outdoor sample.
The laboratory results and chain of custody is attached to this report in Attachment 1,
Laboratory Results and Chain of Custody.
Fungal Tease Tape Sample Results
The fungal tease tape was collected from the supply diffuser in the work out room. Results
are as follows:
Spore Type
Results
Alternaria
Rare 1-10 count
Bipolaris
Rare 1-10 count
Cladosporium
High >1000 count
The high count of Cladosporium is indicative of possible fungal growth in the air handler
and supply ductwork. More investigation would be required to inspect the ductwork and air
handler.
•
•
•
•
Mr. Rick DeGardner
Lino Lake Police Department
Indoor Air Quality and Fungal Sampling Results
IHSC Project Number: M20-694
May 6, 2020
Page 5 of 7
ASHRAE Common Indoor Air Quality Parameters
Common IAQ parameters were recorded in the locker room and Deputy Director's office
using a TSI IAQ Calc. The data statistics for the two areas are summarized as follows:
Locker Room:
are ITlete-
very
Mu
Temperature (F)
70.3
69.5
70.9
Relative Humidity (%)
40
38.7
42
Carbon Dioxide (ppm)
445
438
458
Carbon Monoxide (ppm)
0.0
0.0
0.0
F = Fahrenheit, % = Percent, ppm = parts per million
Deputy Director's Office:
Parameter
Average.
J Minimum
Maximum:
Temperature (F)
72.1
71,5
72.5
Relative Humidity (%)
36.9
36.2
38.3
Carbon Dioxide (ppm)
426
420
452
Carbon Monoxide (ppm)
0.0
0.0
0.0
The ASHRAE recommend levels for temperature, relative humidity, carbon monoxide (CO),
and carbon dioxide (CO2). The Occupational Safety and Health Administration (OSHA) set
standards for CO, CO2, and guidelines for temperature, and relative humidity.
Temperature and Relative Humidity
The ASHRAE and OSHA both recommend ambient room temperature between 68°
Fahrenheit (F) to 76° F. The average, minimum and maximum temperatures in the two
areas were within the recommended range.
The ASHRAE recommend a relative humidity level between 30% and 70% and OSHA
recommends a level between 20% and 60%. The average humidity level in both areas
were with in recommended ranges.
Mr. Rick DeGardner
Lino Lake Police Department
Indoor Air Quality and Fungal Sampling Results
IHSC Project Number: M20-694
May 6, 2020
Page 6 of 7
Carbon Dioxide
Carbon dioxide, a product of combustion and human respiration, is a commonly used
indicator of overall air quality and ventilation rates within an occupied building. The levels
found in buildings are primarily a function of the rate and amount of outside air delivery to
the occupied space, the effectiveness of air distribution within the space, and the
occupancy of the space. Moderate to elevated levels of carbon dioxide can cause
headaches and fatigue, and higher concentrations can produce nausea, dizziness, and
vomiting.
Loss of consciousness can occur at extremely high concentrations. To prevent or reduce
high concentrations of carbon dioxide in a building or room, fresh air should be supplied to
the area.
The ASHRAE recommends a CO2 level below 1,000 ppm and OSHA, based on the
National Institute for Occupational Safety and Health recommendations of between 600
ppm for minimal air quality complaints, and 1,000 ppm as an upper limit for indoor levels.
OSHA also has a Permissible Exposure Limit (PEL) Time Weighted Average (TWA) of
5,000 ppm. The average CO2 levels for both areas were below OSHA minimal air quality
complaint level of 600 ppm.
Carbon Monoxide
Carbon monoxide typically is a product of incomplete combustion, is a chemical asphyxiant
at high concentrations, and can cause flu like symptoms that clear up after leaving the
contaminated space. The ASHRAE recommends a CO level below 9 ppm in an office
setting, and OSHA sets a PEL TWA over an eight -hour period of 35 ppm. The minimum,
maximum, and average CO readings for both office areas tested were all 0 ppm.
CONCLUSIONS AND RECOMMENDATIONS
The results of the fungal spore samples showed that there is not an indoor fungal air quality
problem in the two locations that were sampled. All the indoor air quality parameters were
also within all regulations and recommendations.
The only abnormal results were the fungal tease tape sample collected from the supply
diffuser. The black dust/residue had a high concentration of Cladosporium. At a minimum,
IHSC would recommend getting the supply diffusers cleaned. Cleaning should be conducted
with a high efficiency particulate air filtered vacuum and wet wiping methods to ensure that
the fungal spores are not released into the areas below. If after the cleaning the black
•
Mr. Rick DeGardner
Lino Lake Police Department
Indoor Air Quality and Fungal Sampling Results
IHSC Project Number: M20-694
May 6, 2020
Page 7 of 7
dust/residue comes back then ductwork cleaning and air handler cleaning may be needed.
In conclusion the black dust/residue was built up in the ductwork over time and when the
HVAC flow was tested at a higher than normal flow the dust/residue came loose and was
blown out the supply diffusers. Since there is no current fungal indoor air quality problem,
cleaning the diffusers is our only recommendation at this time.
Results presented are based on analysis in accordance with currently accepted industrial
hygiene practices at this time and location. Other than this, no guarantee is implied or
intended.
We appreciate the opportunity to be of service to you. If you have any questions regarding
this report, please contact me at (651) 287-5373.
Sincerely,
INDUSTRIAL HYGIENE SERVICES CORPORATION
Nicholas S. Mueller
Senior Project Manager
Attachment (1). Laboratory Results and Chain of Custody
ATTACHMENT 1
Laboratory Results and Chain of Custody
•
•
•
EMSL Analytical, Inc.
3410 Winnetka Avenue North New Hope, MN 55427
Tel/Fax: (763) 449-4922 / (763) 449-4924
http://www.EMSL.com / minneapolislab a(�emsl.com
EMSL Order: 352004154
Customer ID: IHSC80
Customer PO:
Project ID:
Attention: Nick Mueller
Industrial Hygiene Services Corporation
4205 White Bear Parkway
Suite 500
Vadnais Heights, MN 55110
Project: M20-694, Lino Lakes Police Department
Phone:
Fax:
Collected Date:
Received Date:
Analyzed Date:
(651) 766-9811
(651) 766-9822
04/28/2020
04/28/2020
05/04/2020
Test Report: Microscopic Examination of Fungal Spores, Fungal Structures, Hyphae, and Other Particulates
from Tape Samples (EMSL Method MICRO-SOP-200)
Lab Sample Number:
Client Sample ID:
Sample Location:
352004154-0004
04TT
Supply Diffuser in workout
Room
Spore Types
Category
Alternana (Ulocladium)
Ascospores
Aspergillus/Penicillium
Basidiospores
Bipolaris++
Chaetomium
Cladosporium
Curvularia
Epicoccum
Fusarium
Ganoderma
Myxomycetes++
Pithomyces++
Rust
Scopulariopsis/Microascus
Stachybotrys/Memnoniella
Unidentifiable Spores
Zygomycetes
Rare
-
-
-
Rare
-
*High*
-
-
-
-
-
-
-
-
-
-
-
Hyphal Fragment
Insect Fragment
Pollen
-
-
Rare
Category: Count/per area analyzed - Rare: 1 to 10 Low: 11 to 100 Medium: 101 to 1000 High: >1000
- Denotes Not Detected.
++ Includes other spores with similar morphology; see EMSL's fungal glossary for each specific category.
= Sample contains fruiting structures and/or hyphae associated with the spores.
No discernable field blank was submitted with this group of samples.
Jodie Bourgerie, Laboratory Manager
or other Approved Signatory
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsbilily of the client This report relates only to the samples reported above and may not be reproduced,
except in full, without written approval by EMSL EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. When the information
•supplied by the customer can affect the validity of the result, 1 will be noted on the report.
Samples analyzed by EMSL Analytical, Inc. New Hope, MN AIHA-LAP, LLC—EMLAP Accredited #101103
Initial report from: 05/04/2020 12:10 PM
For information on the fungi listed in this report, please visit the Resources section at www.emsl.com
Test Report DEVER1-2.9.0 Printed 05/04/2020 12:10 PM
Page 1 of 1
EMSL Analytical, Inc.
3410 Winnetka Avenue North New Hope, MN 55427
Tel/Fax: (763) 449-4922 / (763) 449-4924
http://www.EMSL.com / minneapolislabt�emsl.com
EMSL Order: 352004154
Customer ID: IHSC80
Customer PO:
Project ID:
r
Attention: Nick Mueller
Industrial Hygiene Services Corporation
4205 White Bear Parkway
Suite 500
Vadnais Heights, MN 55110
Project: M20-694, Lino Lakes Police Department
Phone:
Fax:
Collected Date:
Received Date:
Analyzed Date:
(651) 766-9811
(651) 766-9822
04/28/2020
04/28/2020
05/04/2020
Test Report: Aflergenco-D(T") Analysis of Fungal Spores & Particulates by Optical Microscopy (Methods MICRO-SOP-201, ASTM D7391)
Lab Sample Number:
Client Sample ID:
Volume (L):
Sample Location:
352004164-0001
01M
150
Locker Room
352004154-0002
02M
150
Deputy Director Office
352004154-0003
03M
150
Exterior of Building
Spore Types
Raw Count Count/m' % of Total
Raw Count CounUm' % of Total
Raw Count Count/in' % of Total
Altemaria (Ulocladium)
Ascospores
Aspergillus/Penicillium
Basidiospores
Bipolans++
Chaetomium
Cladosponum
Curvularia
Epicoccum
Fusarium
Ganoderma-
Myxomycetes++
Pithomyces++
Rust
Scopulanopsis/Microascus
Stachybotrys/Memnoniella
Unidentifiable Spores
Zygomycetes
Total Fungi
Hyphal Fragment
Insect Fragment
Pollen
- - -
1 20 74.1
- - -
- - -
- - -
1* 7* 25.9
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
2 27 100
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
5' 30* 100
- - -
- - -
- - -
- - -
- -
- - -
- - -
- - -
- - -
- - -
5 30 100
- - -
- - -
- - -
1 20 0.5 .
142 3140 76.4
11 240 5.8
29 640 15.6
- - -
3 70 1.7
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
186 4110 100
- - -
_ -
1* 7* -
Analyt Sensitivity 600x
Analyt. Sensitivity 300x
Skin Fragments (1-4)
Fibrous Particulate (1-4)
Background (1-5)
- 22 -
- 7' -
- 1 -
- 1 -
- 2 -
- 22 -
- 7' -
- 1 _
- 1 -
- 1 -
- 22 -
- 7* -
- - -
- 1 -
- 1 -
++ Includes other spores with similar morphology: see EMSL's fungal glossary for each specific category.
Jodie Bourgerie, Laboratory Manager
or other Approved Signatory
No discernable field Mardi was submitted with this group of samples.
High levels of background particulele can obscure spores and other particulates, leading to underestimation. Background levels of 5 Indicate an overloading of background particulates, prohibiting accurate detection and quantification.
Present = Spores detected on overloaded samples. Results are not blank corrected unless otherwise noted. The detection limit is equal to one fungal spore, structure, pollen, fiber panicle or insect fragment. -'- Denotes particles found
al 300X. "•" Denotes not detected. Due to method stopping rules, raw counts in excess of 100 are extrapolated based on the percentage analyzed. EMSL maintains liability bmded to cost of analysis. Interpretation and use of test
results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL EMSL bears no responsibility for sample collection
activities or analytical method limitations. The report reflects the samples as received. When the information supplied by the customer can affect the validity of the result, it will be noted on the report.
Samples analyzed by EMSL Analytical, Inc. New Hope, MN AIHA-LAP, LLC—EMLAP Accredited #101103
Initial report from: 05/D4/2020 12;10 PM
For information on the fungi listed in this report, please visit the Resources section at www.emsl.com
Test Report - emsl_Micro_SporeTrap_Ver3_0002 Printed 05/04/2020 12:10 PM
Page 1 of 1
OrderlD: 352004154
11V000 I rum_
Suite 500
HYGIENE CHAIN - OF
SERVICES 651-766-9811
- CUSTODY RECORD Vadnais heights, MN 55110
'
rf1RPf1RATICIN
LAB NAME L, r L
LAB USE ONLY
LABORATORY PROJECT NO
LABORATORY
SAMPLE
NUMBER
(- TOTAL NUMBER OF CONTAINERS
w
w
DATE
w
5 RELINQUISHED BY (SIGNATURE)
COMPANY
6 RECIEVEO BY (SIGNATURE)
COMPANY
z
0
5
z „
8o >.-
pa0
p,,
" cS3 N
SAMPLE
CONDMON/
COMMENTS
a- loans
V-id&XXV
SaaNIV.LNOD
JO 213HWMI
ANALYSIS REQUESTED
TT = Tease Tape Lift
1r
al
w
TUOW al PIOW
X
3 RELINQUISHED BY (SIGNATURE)
COMPANY
4 RECIEVED BY (SIGNATURE)
COMPANY
'MIN MIN
X
X
aatu.(o)
`soan(n)s `snoan(D)v'xnn(e)
'an(v) Wit -xia.tvi+i 31dt4Vs
<
<
<
r
1
L.
0
w
0
1RNAROUND REQUESTED
NORMAL 96 Hour
RUSH
OTHER
DATE /TIME SAMPLED
04/28/20 150 L
04/28/20 150 L
04/28/20 150 L
04/28/20
a
SAMPLE LOCATION / DESCRIPTION
Locker Room
6
Exterior or Building
Supply Diffuser tiN voarkle.per �
IHSC PROJECT NO M20-694
PROJECT MANAGER Nicholas Mueller
PROJECT NAME Lino Lakes
ea
Or
u
0
a
C
PROJECT LOCATION Lino Lake ,MN
SAMPLERS SIGNA
4.!
‹...___x
_---
2 ED BY (SIGNATURE)
3
d
w
It
v,
0
0
0
04TT
Page 1 Of 1
NI n r6
Stephen Kotzmacher
1001 Labore Industrial Court, Suite B
Vadnais Heights, MN 55110
651-255-3527 Direct
651-230-8971 Cell
skotzmacher@nac-hvac.com
May 19, 2020
City of Lino Lakes
600 Town Center Parkway
Lino Lakes MN 55014-1182
Re: Police Station Duct Cleaning
NAC Proposes to sub -contract KMS Air Duct Cleaning. KMS will clean the Police Stations supply
duct, return duct, and diffusers. This work is defined on the drawings and photos provided by NAC.
This work will be done to NADCA standards. NAC will clean the remaining diffusers in the City Hall
and ECL area.
KMS Services Includes:
• Coordination with Client
• Clean diffusers
• Clean supply and return air ducts
• Clean up of work area
NAC Services Includes:
• Coordination with Client
• Clean diffusers in ELC and City Hall
• Clean up of work area
Client base investment: $11,065.00 (Eleven Thousand Sixty Five -Dollars and 00/100)
Notes:
1. Proposal based upon normal working hours.
2. Any required code upgrades or modifications required will be performed at time and
material upon proper approval.
3. Proposal price is valid for a period not to exceed (30) calendar days.
Accepted by:
CITY OF LINO LAKES NAC MECHANICAL & ELECTRICAL SERVICES
Signature: Signature: 6tephen 9(ptLseacfiet
Name: Justin Williams Name: Stephen Kotzmacher
Title: Utility Supervisor Title: Account Manager
Date: Date: 5/19/2020
Mechanical o Electrical Fabrication 4 Building Technology : 24 Hour Service
•
•
•
CITY COUNCIL
AGENDA ITEM 5B
STAFF ORIGINATOR: Diane Hankee, City Engineer
MEETING DATE: May 26, 2020
TOPIC: Resolution No. 20-48, Accepting Quotes and Awarding a
Construction Contract, 12th Avenue Trail Project
VO I REQUIRED: 3/5 Vote Required
INTRODUCTION
Staff is requesting authorization to accept quotes and award the construction contract for the
12th Avenue Trail Project.
BACKGROUND
The City received resident requests to construct a trail along 12th Avenue. The Council directed
staff to prepare a preliminary design and cost estimates. The trail was discussed at City Council
work sessions throughout 2019 and as a result the City Council budgeted for this project within
their 2020 budget. Staff has requested quotes for the construction of the 12th Avenue Trail
project.
The 12th Avenue Trail Project includes construction of a new trail between White Oak Road and
the existing trail head approximately 720 feet south of White Oak Road, pedestrian ramp
improvements, and ditch grading and culvert repairs to facilitate drainage in the project area. A
location map is enclosed. The project is funded through the park and trail improvement fund in
the amount of $125,000 and through state aid in the amount of $25,000.
Quotes for the project were received on May 19th, 2020.
CONTRACTOR
TOTAL QUOTE
Allied Blacktop Co.
Did Not Quote
Asphalt Concrete Solutions
Did Not Quote
Bituminous Roadways Inc.
$150,703.30
The engineers estimate for the project was $148,000.00 . The low bid was submitted by
Bituminous Roadways Inc. of Mendota Heights, MN in the amount of $150,703.30. The
completion date for this project is October 15th, 2020.
•
•
•
RECOMMENDATION
Staff recommends adoption of Resolution No. 20-48 accepting quotes and awarding a construction
contract for the 12th Avenue Trail Project, in the amount of $150,703.30 to Bituminous
Roadways Inc.
ATTACHMENTS
1. Resolution No. 20-48
2. Quote
3. Figure 1 — Location Map