HomeMy WebLinkAboutLI4 - CONTROLLER NOTE:
REFER TO WRTTTEN SPECIFICATION SECTION OF THE CURRENTLY
APPROVED PERFORMANCE-BASED PLANTING IRRIGATION
SPECIFICATION (32 84 00) FOR ADDITIONAL REQUIREMENTS
VALVE BOX AND COVER
PEDESTAL IRRIGATION -
CONTROLLER FINISHED GRADE VALVE WITH FLOW CONTROL
AND PRE-INSTALLED SOLENOID.
0
WATERPROOF WIRE
CONNECTIONS DBR OR EQUAL LATERAL LINE,
X/�__SEE SPECS FOR DEPTH
SLOPE TO DRAIN SINGLE STATION DECODER
ONE DECODER PER VALVE.
Hill FINISHED GRADE CONTINUOUS
BRICK SUPPORT
CONCRETE FOOTING TTTWO-WIRE SIGNAL WIRE
CONDUIT FOR ELECTRICAL POWER FROM CONTROLLER GRAVEL (4' MIN.)
CONDUCTORS PER LOCAL AND
NATIONAL CODE
CONDUIT FOR
GROUND WIRE MAIN LINE LENGTH
CONDUIT FOR REMOTE AS REQUIRED
CONTROL VALVES AND
SENSOR WIRES
FRONT RIGHT-SIDE NOTE:
SECTION ELEVATION SECTION ELEVATION 1 . INSTALLATION TO BE COMPLETED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS
AND BEST PRACTICES.
NOTE: 2. SET VALVE BOXES AT FINAL GRADE OR HIGHER AS LANDSCAPE INDICATES SO THAT THEY
1 . INSTALLATION TO BE COMPLETED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS ARE VISIBLE BUT NOT A HAZARD.
AND BEST PRACTICES. 3. VALVE BOX BOTTOMS ARE TO BE SUPPORTED ON BRICKS OR SUITABLE HARD MATERIAL TO
2. HIGH AND LOW VOLTAGE ELECTRICAL WORK IS TO BE PERFORMED BY A LICENSED ELECTRICIAN PREVENT BOXES FROM BEING PUSHED BELOW GRADE.
3. GROUND CONTROLLER IN ACCORDANCE WITH MANUFACTURER RECOMMENDATION, 4. INSTALL CONTROLS VALVE IN PROPER IRRIGATION BOXES, AS PER INDUSTRY STANDARDS
FOR EASE OF SERVICE AND MANUAL OPERATION. SEE IRRIGATION SPECIFICATION.
5. UTILIZE EXTENSION KITS AS REQUIRED.
6. ADD FOUR-INCHES OF 3/4-INCH CRUSHED GRAVEL SUMP PER BOX.
7. ALLOW FOR NOT LESS THAN 24" WIRE SLACK COILED NEATLY IN CONTROL BOX.
2-WIRE PEDESTAL CONTROLLER SAMPLE 3 VALVE W/ SOLENOID AND DECODER SAMPLE 2
'fHE ci't*)' c 1: 5TH STREET CORRIDOR
LAKE ELMO STANDARD DETAILS IRRIGATION DETAILS L14
JUNE 2016