HomeMy WebLinkAbout09 - 2019-10-10 Lake Elmo Senior Development- Preliminary Plan Review PAGE 1 of 2
MEMORANDUM
Date: October 10, 2019
To: Ken Roberts, Planning Director Re: Lake Elmo Senior Development
Cc: Chad Isakson, Assistant City Engineer Preliminary Plan Review
From: Jack Griffin, P.E., City Engineer
Engineering has reviewed the Preliminary Site Plan for the Lake Elmo Senior Development to be located along 39th
Street North, just east of Arbor Glenn Senior Living. The submittal consisted of the following documentation received
September 30, 2019:
Preliminary Site Plan and PUD dated September 17, 2019, prepared by Ayres Associates.
Storm Water Management Plan dated September 17, 2019 prepared by Ayres Associates.
Traffic Impact Study dated August 30, 2019 prepared by Ayres Associates.
Engineering review comments are as follows:
Final Construction Plans and Specifications must be prepared in accordance with the latest version of the City
Engineering Design Standards Manual, using City details, plan notes and specifications and meeting City Engineering
Design Guidelines. A detailed construction plan review will be completed prior to the start of construction of the site
improvements.
STREETS AND TRANSPORTATION
Site Access/Access Management is sufficient. With the potential for many new commercial buildings along
39th Street North, access management will need to be carefully implemented to ensure that 39th Street
continues to function as intended. As parcels develop and subdivide, the access points to 39th Street will need
to be coordinated and minimized. The site plan has been revised to show only one driveway access to the
development. The proposed access meets the acceptable spacing guidelines from the existing driveway at
Arbor Glen and maintains an adequate offset from the south leg of Laverne Avenue.
39th Street North Right‐of‐Way Dedication not required. No additional right‐of‐way dedication appears to be
required along 39th Street North. The preliminary plan shows that the existing right‐of‐way provides a
minimum of 40 feet from street centerline along the entire length of the property.
39th Street North Utility Easement Dedication. A 10‐foot utility easement for small utilities has been dedicated
to the City along the entire north boulevard of 39th Street North. The site plans must be prepared in a manner
to preserves the full 10‐feet for small utility installation with no obstructions (e.g. signs, trees, structures, etc.).
The preliminary plan must be revised to show the utility easement graded as boulevard with maximum 4%
slope.
Construction parking and staging (preservation of 39th Street North). As part of any development or site
improvement agreement the developer will be required to manage all construction parking, construction
staging and material deliveries internal to the site. No parking and construction staging, including loading and
unloading materials and equipment will be allowed along 39th Street North at any time during the construction
of the site improvements and buildings. All street and boulevard damage caused by the construction activities
must be repaired or replaced at no cost to the City and meeting City standards and specifications.
FOCUS ENGINEERING, inc.
Cara Geheren, P.E. 651.300.4261
Jack Griffin, P.E. 651.300.4264
Ryan Stempski, P.E. 651.300.4267
Chad Isakson, P.E. 651.300.4285
PAGE 2 of 2
Site easements/landscaping. The preliminary plans must be revised to maintain all tree plantings outside of
the front, side and rear drainage and utility easements.
Traffic Impact Study. A traffic impact study has been submitted as part of the site plan application. The Study
findings indicate no additional travel lanes, turn lanes or other road improvements required.
STORMWATER MANAGEMENT
A State and Valley Branch Watershed District (VBWD) permit will be required. The site plan is subject to a storm
water management plan meeting State, VBWD and City rules and regulations.
Storm water facilities proposed for meeting permitting requirements must be designed and constructed in
accordance with the City Engineering Design Standards Manual available on the City website.
Based on the plans received to date, plan revisions are required to conform the site design to VBWD and City
rules and regulations.
The storm water facilities constructed for this development should remain privately owned and maintained.
The applicant will be required to execute and record a Stormwater Maintenance and Easement Agreement in
the City’s standard form of agreement.
The storm water facility 100‐year HWL must be fully contained within the subject property and must be a
minimum of 2‐feet below all adjacent low floor building elevations.
The existing downstream drainage basins for the 39th Street storm sewer system do not have available
treatment or storage capacity to accommodate new development. Therefore, any storm sewer connections to
the 39th Street system must be at both reduced runoff rates and volumes.
Connection to 39th Street storm sewer requires verification of existing capacity within all downstream storm
sewer systems and availability of downstream storm sewer ponding at the discharge location(s). Detailed
storm sewer calculations must be submitted demonstrating sufficient capacity and meeting all current City
Engineering Design Standards.
MUNICIPAL WATER SUPPLY
The proposed property is located in the Old Village MUSA and intermediate water system pressure zone.
Connection to the municipal water supply is readily available to serve this property. The applicant will be
required to connect, at its sole cost, to the existing 8‐inch DIP stub that was installed to serve this property. A
minimum 8‐inch diameter watermain will be required to be extended internal to the site with private water
services stubbed for connection to each individual building.
The applicant will be responsible to place hydrants and gate valves throughout the property at the direction of
the Fire Department and Public Works Department (see attached hydrant and system valve locations). All fire
hydrants and connecting watermains shall be owned and maintained by the City.
Any watermain lines and hydrants placed internal to the site will require minimum 30‐foot easements centered
over the hydrant or pipe. Easements must be dedicated to the City and be provided in the City’s standard form
of easement agreement.
Water availability charges and connection charges will apply to the service connections. A Met Council SAC
determination will be required to determine the WAC/Connection charges for each building.
MUNICIPAL SANITARY SEWER
The proposed property is located in the Old Village MUSA current Regional Sewer Staging Plan and would
discharge to the MCES Cottage Grove Ravine Interceptor.
Connection to the municipal sanitary sewer system is readily available to serve this property. The applicant will
be required to connect, at its sole cost, to the existing 8‐inch PVC stub that was installed to serve this property.
An 8‐inch diameter sanitary sewer main will be required to be extended internal to the site with private sewer
service stubs installed for connection to each individual building.
All sanitary sewer mains internal to the site shall remain privately owned and maintain.
The sanitary sewer main along the south property line must be realigned to remain outside of the 10‐foot
drainage and utility easement (see attached sanitary sewer realignment).
Sewer availability charges and connection charges will apply to the service connections. A Met Council SAC
determination will be required to determine the SAC/Connection charges for each building.
1036
1044
1091
1115
WV
SAN
MH
1166
SAN
MH
1177
WV
STM
MH
1182
WV
STM
MH
1186
ETRAN
ETRAN
WV
1254
IP1/2" RB
SAN
MH
1366
IP
MH
IPIP
G G G G G G G G G
E E E E E E E EEEEEEEEE
EEE
SAN SAN SAN SAN
SAN SAN SAN SAN SAN SAN
STM STM STM STM STM
STM STM STM STM STM STM
W W W W W W W W
W W
SA
N
W
W
W
W
W
SA
N
SA
N
SA
N
SA
N
SA
N
W
W
W
W
W
W
W
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SAN
MH
SAN
SAN
SAN
W W W W
SUBSURFACE
INFILTRATION
SYSTEM (50'x85')
SUBSURFACE
INFILTRATION
SYSTEM (70'x50')
DS DS DS
DS DS DS DS DS
DS DS
DS DS DS DS
DS
DS
DS
DS DS
DS
DS
DS DS DS DS DS
DS DS DS
DS
DSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDS
DS
S15
S12
S13
S14
S11
S17
S10
S09
AEW1
S08
S06
S07
AEW2
S04
S03
S05
S01
S02
S26
107' -
1
2
"
S
S
@
0
.
5
0
%
152' - 18" SS @ 0.22%
46' - 18" SS @ 0.22%
8
2
'
-
1
8
"
S
S
@
0
.
2
2
%
58' - 18" SS @ 0.22%
129' - 12" SS @ 0.37%
7
0
'
-
1
2
"
S
S
@
0
.
5
0
%
107' - 15" SS @ 0.50%
56' - 18" SS @ 0.22%
11' - 12" SS @ 5.00%
52' - 15" SS @ 1.80%
40' - 12" SS @ 1.15%
96' - 12" S
S
@
2
.
2
4
%
55' - 15" SS @ 0.28%
18
7
'
-
1
5
"
S
S
@
0
.
2
8
%
23' - 12" SS @ 0.37%
35' - 15" SS @ 0.37%
39' - 12" SS @ 0.37%
S19
S18
CONNECT TO EXISTING CONNECT TO EXISTING
CONNECT TO EXISTING
CS
CS
T
T
CS
CS
T
T
CS
CS
T
T
CS
CS
T
T
T
CS
CS
CS
T
T
CS
CS
T
T
CS
CS
T
T
CS
CS
T
T
33' - 12" SS @ 0.37%
34' - 15" SS @ 0.28%
S30
S31
SITE UTILITIES LEGEND
1.ALL WATERMAIN AND ACCESSORIES MUST BE CONSTRUCTED IN ACCORDANCE WITH THE CITY OF LAKE ELMO
STANDARD SPECIFICATIONS AND DETAILS.
2.MANIPULATION OF EXISTING VALVES SHALL BE PERFORMED ONLY BY CITY PERSONNEL.
3.WATERMAIN SHALL BE DUCTILE IRON PIPE, ENCASED IN POLYETHYLENE, CLASS-52.
4.ALL FITTINGS SHALL COMPLY WITH CEAM SPEC. 2611.2.A.1. ALL FITTINGS SHALL BE DUCTILE IRON PIPE WITH
POLYETHYLENE ENCASEMENT. ALL CONNECTIONS SHALL BE INSTALLED UTILIZING COR-BLUE NUTS & BOLTS.
5.USE GATE VALVES FOR ALL APPLICATIONS UP THROUGH 12 INCHES.
6.GATE VALVES SHALL BE RESILIENT WEDGE AMERICAN FLOW CONTROL SERIES 2500 OR APPROVED EQUAL.
GATE VALVES MUST COMPLY WITH CEAM SPEC 2611.2.C.2.
7.USE BUTTERFLY VALVES FOR ALL APPLICATIONS GREATER THAN 12 INCHES.
8.BUTTERFLY VALVES SHALL BE MUELLER LINSEAL III, OR APPROVED EQUAL. BUTTERFLY VALVES SHALL
COMPLY WITH CEAM SPEC. 2611.2.C3.
9.BOLTS AND NUTS ON ALL VALVES AND HYDRANTS SHALL BE STAINLESS STEEL.
10.ALL HYDRANTS SHALL BE INSTALLED 5.0 FEET BACK OF CURB.
11.HYDRANTS SHALL BE WATEROUS "PACER," MODEL WB-67 OR APPROVED EQUAL, FITTED WITH FH 800 SERIES
FLEX STAKE AND PAINTED RED.
12.HYDRANTS SHALL HAVE TWO OUTLET NOZZLES FOR 2-1/2 (I.D.) HOSE CONNECTIONS AND ONE 4" STORZ
NOZZLE (MODEL WB-67) AND PENTAGON NUT END CAP.
13.THE CURB STOP SERVICE ASSEMBLY SHALL HAVE A MINIMUM 1-FT ADJUSTMENT RANGE AND SHALL EXTEND 6
INCHES ABOVE FINISHED GRADE FULLY EXTENDED.
14.THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING WATER TO HOMES AND BUSINESSES WHOSE
WATER SUPPLY IS DISRUPTED DURING THE COURSE OF THE PROJECT.
1.ALL SANITARY SEWER AND ACCESSORIES MUST BE CONSTRUCTED IN ACCORDANCE WITH THE CITY OF LAKE
ELMO STANDARD SPECIFICATIONS AND DETAILS.
2. ALL SANITARY SEWER PVC PIPE SHALL BE INSTALLED ACCORDING TO CITY STANDARD DRAWING 103
"GRANULAR MATERIAL BEDDING METHOD (FOR PVC SANITARY SEWER PIPE).
3.UNLESS NOTED OTHERWISE, ALL SMOOTH WALLED SANITARY SEWER PVC PIPE AND FITTINGS SHALL BE SDR
35 WITH ELASTOMERIC GASKETED JOINTS.
4.ALL SANITARY SEWER SERVICES SHALL BE 4-INCH PVC, SCH. 40.
5.SMOOTH WALLED PVC PIPE AND FITTINGS SHALL CONFORM WITH THE REQUIREMENTS OF ASTM D-3034 FOR
THE SIZE, STANDARD DIMENSION RATIO (SDR), AND STRENGTH REQUIREMENTS INDICATED ON THE PLANS,
SPECIFICATIONS, AND SPECIAL PROVISIONS.
6.REINFORCED CONCRETE PIPE AND FITTINGS SHALL CONFORM WITH THE REQUIREMENTS OF MnDOT SPEC
3236 (REINFORCED CONCRETE PIPE) FOR THE TYPE, SIZE, AND STRENGTH CLASS SPECIFIED HEREIN.
7.JOINTS OF MANHOLE RISER SECTIONS SHALL BE TONGUE AND GROOVE WITH RUBBER "O" RING JOINTS
PROVIDED ON ALL SANITARY SEWER MANHOLES.
8.SANITARY SEWER INLET AND OUTLET PIPES SHALL BE JOINED TO THE MANHOLE WITH A GASKETED, FLEXIBLE,
WATERTIGHT CONNECTION TO ALLOW DIFFERENTIAL SETTLEMENT OF THE PIPE AND MANHOLE TO TAKE PLACE.
9.A 1'-0" TO 1'-4" MANHOLE SECTION SHALL BE INSTALLED UNDER THE CONE SECTION TO ALLOW FOR HEIGHT
ADJUSTMENT WHENEVER POSSIBLE.
10.ALL SERVICE LINE STUBS MUST HAVE A 2"x2" HARDWOOD MARKER WITH METAL SPIKE RUNNING FROM THE
END OF PIPE TO FINISHED GRADE ELEVATION.
11.UPON MAKING A CONNECTION TO AN EXISTING SANITARY SEWER STUB OR MANHOLE, DIRT AND DEBRIS
SHALL BE PREVENTED FROM ENTERING THE EXISTING SEWER BY IMMEDIATELY INSTALLING WATERTIGHT PLUGS
AS NEEDED IN THE EXISTING MANHOLE.
12.ALL MAINLINE SANITARY SEWER AND SERVICES SHALL HAVE TRACER WIRE PER CITY SPECIFICATIONS AND
DETAILS.
1.ALL STORM SEWER AND ACCESSORIES MUST BE CONSTRUCTED IN ACCORDANCE WITH THE CITY OF LAKE
ELMO STANDARD SPECIFICATIONS AND DETAILS.
2.REINFORCED CONCRETE PIPE AND FITTINGS SHALL CONFORM WITH THE REQUIREMENTS OF MnDOT SPEC
3236 (REINFORCED CONCRETE PIPE) FOR THE TYPE, SIZE, AND STRENGTH CLASS SPECIFIED HEREIN.
3.PRECAST CONCRETE MANHOLE AND CATCH BASIN SECTIONS SHALL CONFORM TO THE REQUIREMENTS OF
ASTM C-477.
4.A 1'-0" TO 1'-4" MANHOLE SECTION SHALL BE INSTALLED UNDER THE CONE SECTION TO ALLOW FOR HEIGHT
ADJUSTMENT WHENEVER POSSIBLE..
5.JOINTS OF MANHOLE RISER SECTIONS SHALL BE TONGUE AND GROOVE WITH RUBBER "O" RING JOINTS
PROVIDED ON ALL STORM SEWER MANHOLES..
6.RIP-RAP SHALL BE HAND-PLACED OVER GEOTEXTILE FABRIC AND CONFORM TO MnDOT SPEC. 3601, CLASS III,
OR AS SPECIFIED HEREIN.
7.THE GEOTEXTILE FABRIC USED UNDER RIP-RAP SHALL EXTEND 3 FT UNDER THE APRON.
8.FURNISH & INSTALL TRASH GUARDS ON ALL FLARED END SECTIONS.
9.ALL SILT SHALL BE CLEANED OUT FROM THE RIP-RAP AT THE END OF THE PROJECT.
10.STORM SEWER STRUCTURES WITHIN 10 FT OF WATERMAIN ARE TO HAVE WATER TIGHT CONNECTIONS PER
MDH REQUIREMENTS.
11.ALL NEW STORM SEWER PIPE SHALL BE FLUSHED AND TELEVISED PRIOR TO SUBSTANTIAL COMPLETION - SEE
SPECIFICATION SECTION 1700 - CLOSEOUT REQUIREMENTS.
PROPOSED WATER MAIN, SEE DTLS
207A/C800, 210/C800, 201/C800, &
206/C800
PROPOSED SANITARY SEWER,
SEE DTLS 1/C803, & 2/C803
PROPOSED STORM SEWER,
SEE DTLS 4/C803, 5/C803,
6/C803, 7/C803, & 8/C803
SAN
TRACER WIRE
ACCESS BOXT
CLEANOUT
CL
O
HYDRANT
INSULATION
REDUCER
GATE VALVE & BOX
WTR SERVICE
& CURB STOP
W BEND
CS
STM MH
INL
APRON ENDWALL
AND RIP RAP
SS AREA
INL
SAN MH
DOWNSPOUTDS
PED LIGHT BOLLARD, SEE ELECTRICAL PLANS
LIGHT POLES, BY OTHERS
SEE ELECTRICAL PLANS
PROPOSED 4" UNDERDRAIN,
SEE DTL 4/C804
LAKE ELMO WATERMAIN STANDARD NOTES
LAKE ELMO SANITARY SEWER STANDARD NOTES
LAKE ELMO STORM SEWER STANDARD NOTES
S 933.02 (15")
NE 933.02 (15")
S19
MH 4-FT
CASTING - J
RIM 939.76
S 933.29 (18")
W 933.54 (15")
NE 933.54 (15")
S15
MH 4-FT
CASTING - H
TC 941.16
E 934.08 (15")
NW 934.33 (12")
S12
INL 2X3-FT
CASTING - H
TC 940.98
SE 935.10 (12")
S13
INL 2X3-FT
CASTING - H
TC 940.42
SW 934.47 (15")
NW 934.57 (12")
E 934.57 (12")
S14
MH 4-FT
CASTING - H
TC 940.30
SE 934.68 (12")
S11
INL 2X3-FT
CASTING - H
TC 939.84
W 936.70 (12")
S17
INL 2.5-FT
CASTING - B6
RIM 939.77
S 933.17 (18")
N 933.17 (18")
S10
MH 4-FT
CASTING - J
RIM 939.44
E 933.68 (18")
SW 933.68 (15")
S09
INL 2X3-FT
CASTING - H
TC 938.71
S 937.15 SEE DETAIL 7/C803
AEW1, 12" A.E., SEE DETAIL 7/C803
NE 935.03 (12")
S08
INL 2.5-FT
CASTING - B6
RIM 938.00
N 933.48 (18")
S 933.48 (18")
E 933.98 (12")
S06
MH 4-FT
CASTING - J
RIM 937.96
N 933.35 (18")
S 933.35 (18")
W 933.35 (18")
E 933.85 (12")
S07
MH 4-FT
CASTING - H
TC 937.93
N 936.70
AEW2, 12" A.E., SEE DETAIL 7/C803
N 933.58 (18")
SE 933.58 (12")
SW 933.58 (15")
S04
MH 4-FT
CASTING - C
RIM 937.76
NW 933.72 (12")
S03
INL 2X3-FT
CASTING - H
TC 937.01
W 934.46 (12")
S05
INL 2.5-FT
CASTING - B6
RIM 937.00
N 933.80 (12")
S01
INL 2X3-FT
CASTING - H
TC 935.88
NE 933.71 (15")
S 933.71 (12")
S02
INL 2X3-FT
CASTING - H
TC 935.91
N 932.50 (15")
S26
CONNECT TO EX SS
CASTING -
939.09
NEW UTILITY STRUCTURES
SW 933.17 (15")
S18
MH 4-FT
CASTING - J
RIM 939.83
W 933.97 (12")
S30
INL 2X3-FT
CASTING - H
TC 938.20
NE 933.77 (15")
SW 934.50 (12")
S31
INL 2X3-FT
CASTING - H
TC 938.74
NO
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
-
PROJECT No:
TH
E
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
N
T
H
E
D
R
A
W
I
N
G
S
A
R
E
T
H
E
P
R
O
P
E
R
T
Y
OF
A
Y
R
E
S
A
S
S
O
C
I
A
T
E
S
.
A
L
L
R
I
G
H
T
S
A
R
E
R
E
S
E
R
V
E
D
.
N
O
D
E
S
I
G
N
S
O
R
P
L
A
N
S
SH
A
L
L
B
E
U
S
E
D
O
R
R
E
P
R
O
D
U
C
E
D
I
N
A
N
Y
F
O
R
M
O
R
B
Y
A
N
Y
M
E
A
N
S
W
I
T
H
O
U
T
WR
I
T
T
E
N
P
E
R
M
I
S
S
I
O
N
O
F
A
Y
R
E
S
A
S
S
O
C
I
A
T
E
S
.
Ea
u
C
l
a
i
r
e
O
f
f
i
c
e
34
3
3
O
a
k
w
o
o
d
H
i
l
l
s
P
a
r
k
w
a
y
Ea
u
C
l
a
i
r
e
,
W
i
s
c
o
n
s
i
n
5
4
7
0
1
(7
1
5
)
8
3
4
-
3
1
6
1
Ri
v
e
r
F
a
l
l
s
O
f
f
i
c
e
21
5
N
.
S
e
c
o
n
d
S
t
r
e
e
t
S
u
i
t
e
2
0
4
Ri
v
e
r
F
a
l
l
s
,
W
i
s
c
o
n
s
i
n
5
4
0
2
2
(7
1
5
)
4
2
6
-
4
9
0
8
Fa
x
:
(
7
1
5
)
4
2
6
-
5
8
6
6
NE
W
I
N
D
E
P
E
N
D
E
N
T
L
I
V
I
N
G
F
A
C
I
L
I
T
Y
LA
K
E
E
L
M
O
I
N
D
E
P
E
N
D
E
N
T
L
I
V
I
N
G
,
L
L
C
LA
K
E
E
L
M
O
,
M
I
N
N
E
S
O
T
A
PR
E
L
I
M
I
N
A
R
Y
-
C
I
T
Y
S
U
B
M
I
T
T
A
L
P
A
C
K
A
G
E
08-1893.00
09.17.2019
MARK DATE DESCRIPTION
NORTH
0 30 60
C500
SITE UTILITIES PLAN