MEMORANDUM <br />Memo To :Mayor and City Council Members <br />From :Ric Minetor, Director of Public Works/City Engineer <br />�� <br />Date :November 2, 1988 <br />Subject :Water Treatment Plant Study - Update <br />During the last few months we have taken water samples and filter <br />media samples in an attempt to determine the problems with the <br />filter plant and an overall course of action for improving filter <br />effectiveness. SEH is scheduled to present their r.rort at the <br />November 21st agenda session. <br />We have already made some charges to our operations and are <br />rev(ewing other operations. We super -chlorinated the filters to <br />clean the media. We have also adjusted the backwash operation to <br />improve the removal of insoluble material filtered out of the <br />water. We are also reviewing the permanganate equipment to <br />insure proper dosage rates for this chemical. The filter beds now <br />appear more uniform and the backwash water appears dirtier than <br />previously ( this would mear. improvement in iron and manganese <br />_ removal). Va will be sampling finished water again to confirm the <br />effectiveness of the filters. <br />The long term outlook for this plant must also address the <br />capacity restriction of our filtering system. Although we rarely <br />operate wells 1,2, and 3 together; when we do we have to bypass <br />filtering of une of thet wells. The plant capacity is only 2000 <br />gallons per minute: The wells each put out 1000 gallons per <br />minute. Additionally, we will need to consider the operation of <br />well 4. Currently we have no i.ron or manganese removal from water <br />produced by well 4. I have aeked SEH to include information <br />regarding this long term outlook in their report. <br />1� <br />