Laserfiche WebLink
JAN-23-01 04 :07 PM CASTLE COS. INC. 651 702 9364 <br /> 37 <br /> 2912 Pentagon,Plan Review <br /> January 18,2001 <br /> Page 2 of 2 <br /> • <br /> 9. At least one of the showers in both locker rooms must comply with the requirements of MSBC Chapter 1341.0458. <br /> 10.-Provide exit signs per.UBC Section 1003.2.8.2, note that the maximum distance between signs is 100 feet. It looks <br /> like you will need one additional at the junction of areas 126,108 and 109: <br /> 11. What is your proposed plan for emergency lighting per UBC Section 1003.2.97 Note that all areas must be <br /> covered. <br /> 12. The rest room in the child care room must also comply with all of the requirements in MSBC Chapter 1341 for <br /> handicap accessibility, clear floor space, grab bars, fixtures, etc. <br /> 13. The counter heights in the juice bar area must comply with the requirements of MSBC Chapter 1341.0520. <br /> 14. Maintain a minimum of 44" clear aisle width to the exit door in the cardio area. <br /> End of Comments <br /> Please respond to these comments by way of addendum and/or revised plans as necessary. <br /> Respect submitted, <br /> Grego o A. S <br /> G g chmtt, C.B.Q., Building Official/City of St. Anthony <br /> • <br />