MECHANICAL AND ELECTRICAL REQUIREMENTS <br />73 <br />cilities in accordance with the ICC Electrical Code. Dwelling <br />units shall be served by a three -wire, 1201240 volt, single- <br />phase electrical service having a rating of not less than 60 am- <br />peres. <br />604.3 Electrical system hazards. Where it is found that the <br />electrical system in a structure constitutes a hazard to the occu- <br />pants or the structure by reason of inadequate service, improper <br />fusing, insufficient receptacle and lighting outlets, improper <br />wiring or installation, deterioration or damage, or for similar <br />reasons, the code official shall require the defects to be cor- <br />rected to eliminate the hazard. <br />SECTION 605 <br />ELECTRICAL EQUIPMENT <br />605.1 Installation. All electrical equipment, wiring and appli- <br />ances shall be properly installed and maintained in a safe and <br />approved manner. <br />605.2 Receptacles. Every habitable space in a dwelling shall <br />contain at least two separate and remote receptacle outlets. Ev- <br />ery laundry area shall contain at least one grounded -type recep- <br />tacle or a receptacle with a ground fault circuit interrupter. <br />Every bathroom shall contain at least one receptacle. Any new <br />bathroomreceptacle outlet shall have ground fault circuit inter- <br />rupter protection. <br />605.3 Lighting fixtures. Every public hall, interior stairway, <br />toilet room, kitchen, bathroom, laundry room, boiler room and <br />furnace room shall contain at least one electric lighting fixture. <br />SECTION 606 <br />ELEVATORS, ESCALATORS AND DUMBWAITERS <br />606.1 General. Elevators, dumbwaiters and escalators shall be <br />maintained to sustain safely all imposed loads, to operate prop- <br />erly, and to be free from physical and fire hazards. The most <br />current certificate of inspection shall be on display at all times <br />within the elevator or attached to the escalator or dumbwaiter; <br />or the certificate shall be available for public inspection in the <br />office of the building operator. <br />606.2 Elevators. In buildings equipped with passenger eleva- <br />tors, at least one elevator shall be maintained in operation at all <br />times when the building is occupied. <br />Exception: Buildings equipped with only one elevator shall <br />be permitted to have the elevator temporarily out of service <br />for testing or servicing. <br />SECTION 607 <br />DUCT SYSTEMS <br />607.1 General. Duct systems shall be maintained free of ob- <br />structions and shall be capable of performing the requited func- <br />tion. <br />18 2003 INTERNATIONAL PROPERTY MAINTENANCE CODE® <br />