Laserfiche WebLink
The Village LLC Development <br />St. Anthony, MN <br />2017-10-02 <br />Fire Code Requirements <br />Fire Code Requirements <br />A. R Occupancies equipped throughout with an approved automatic <br />sprinkler system the fire apparatus access road shall extend to within 600 <br />feet. This is requirement is met. <br />B. Hydrants shall be located to provided coverage of the building pads <br />within a radius of 250 feet. This requirement is met, and depicted on the <br />adjacent figure with 250 foot radius coverage provided. <br />C. Hydrants shall be located within 100 feet of the Fire Department Con- <br />nection (FDC) to the building. This requirement is met. <br />D. Fire apparatus access roads shall be designed to support the imposed <br />loads of fire apparatus and surfaced to provide all-weather driving capabili- <br />ties. This requirement is met, and final turning movements will be reviewed <br />with the Fire Chief prior to approval. <br />E. Dead-end fire apparatus access roads in excess of 150 feet n length shall <br />be provided with an approved area for turning around fire apparatus. This <br />requirement is met by providing a hammerhead conforming to Fire Code <br />requirements.