Laserfiche WebLink
Detail Sheet <br />3. Additional details should be provided for the sanitary sewer services and the insulation over the <br />watermain at storm sewer crossings. <br />• Detail added to detail sheet for insulating over watermain and services. Also added a note to <br />sanitary notes section. <br />4. The sanitary and storm sewer manhole covers shall be ESS Brothers 301 with two concealed pick <br />holes. <br />• Manhole cover details have been revised to call for the ESS Brothers 301 covers. <br />5. Please delete all casting inlet protection options from the plans except for the Wimco. <br />• All other Inlet protection options have been removed. <br />6. Since the silt fence detail does not require any wire mesh to be installed, the post should be noted <br />to be driven a minimum of three feet into the ground. <br />• Detail revised to show a post depth of 36- inches. <br />Please call if you have any additional questions or comments. <br />Sincerely, <br />Craig G. Schlichting, P.E. <br />PLOWE ENGINEERING, INC. <br />6776 Lake Drive NE, Suite 110 <br />Lino Lakes, MN 55014 <br />ph (651) 361-8210 <br />fax (651) 361 -8701 <br />email: craig@plowe.com <br />3 <br />