DEPAR I Men 1 Vr ry of <br />DIVISION OF STATE FIRE MARSHAL <br />MARKET HOUSE <br />289 EAST 5TH STREET <br />ST. PAUL. MINNESOTA 55101 <br />TELEPHONE. 16141 7967641 <br />acility: Little Canada Elementary School <br />Address: 400 Eli Road, Little Canada, MN 55117 <br />4. Within 90 days, replace door in kiln room with a 20 minute rated door assembly, pursuant <br />to: <br />Hie No.; UUGGLJDU <br />Date of Order: 02/06/89 <br />Date of Inspection: 01/06/89 <br />Inspector: Ronald C. Rahman <br />Owner: D. O'Connor <br />Minn. Stat. Sec. 299F.011 (1974). <br />Minnesota Rules 1983, Sec. 7510.0400 <br />Minnesota Uniform Fire Code (MUFC) Sec. 2.303, as amended by <br />Minnesota Rules 1983, Sec. 7510.1200, Subpart 9, <br />NFPA No. 101, Sec. 11- 3.2.1(b), which states: <br />"Rooms or spaces used for the storage, processing, or use of the <br />this section shall be protected in accordance with the following: <br />materials <br />specified in <br />(b) Rooms or spaces used for processing or use of combustible supplies in quantities con- <br />sidered hazardous by the authority having jurisdiction, hazardous materials, or for flam- <br />mable or combustible liquids in quantities deemed hazardous by recognized standards shall <br />be separated from the remainder of the building by construction having not less than a <br />1 -hour fire- resistive rating with all openings protected by self- closing or smoke - actuated <br />fire doors and shall also be protected by an automatic extinguishing system as set forth <br />in Section 6 -4." <br />5. Within 90 days, provide and install an approved storage cabinet for corrosive liquid drums <br />in boiler room, pursuant to: <br />Minn. Stat. Sec. 299F.011 (1974). <br />Minnesota Rules 1983, Sec. 7510.0400 <br />Minnesota Uniform Fire Code (MUFC) Sec. 2.303, as amended by <br />Minnesota Rules 1983, Sec. 7510.1200, Subpart 9, <br />NFPA No. 30, Sec. 4- 3.2.1, which states: <br />"Metal cabinets constructed in the following manner are acceptable. The bottom, top, door <br />and sides of cabinet shall be at least No. 18 gage sheet steel and double walled with 1 <br />1/2 in. air space. Joints shall be riveted, welded or made tight by some equally effec- <br />tive means. The door shall be providwd with a three -point latch arrangement and the door <br />sill shall be raised at least 2 in. above the bottom of the cabinet to retain spilled liq- <br />uid within the cabinet." <br />6 Within 90 days. provide and install maferial with 1 -hour rating in louvre areas of the in- <br />terior corridor, pursuant to: <br />Minn. Stat. Sec. 299F.011 (1974). <br />Minnesota Rules 1983, Sec. 7510.0400 <br />Minnesota Uniform Fire Code (MUFC) Sec. 2.303, as amended by <br />Page 12 <br />FACILITY <br />PS 06017-04 (11 /$fl <br />Page 3 <br />