Laserfiche WebLink
30 <br />ALL ELECTRIC FARM SERVICE (Contd) <br />e. The installation shall not be used to supplement any other system of <br />providing hot water service. <br />f. Company reserves the right to control service to the water heating load. <br />2. The specifications for an Approved Space Heating Installation under this <br />rate are as follows: <br />a. Electric space heating equipment (except 120 volt units individually <br />rated at 15 amperes or less) shall be designed to operate at 240 volts, <br />shall be permanently installed and shall be the sole source of space <br />heating except that provided by fireplaces. <br />b. Not more than 10 kilowatts shall be switched at one time by the <br />heating system controls. <br />c. Company reserves the right to control service to the space heating load. <br />3. Transformer type welding machines larger than 25 kilovolt -amperes will not <br />be permitted on this rate. <br />4. Where two or more farm customers are served from the same transformer, <br />the minimum charge for each customer will be based on the transformer capacity <br />required adequately to serve him, without regard to the transformer capacity <br />actually installed or the minimum charges of other customers served from the <br />same transformer. The Company reserves the right to install load limiting <br />devices for the protection of its transformers and equipment and for the de- <br />termination of the appropriate transformer size. <br />5. Temporary enlargement of transformer capacity for such purposes as corn <br />drying and hay drying shall be treated as Temporary Service. <br />6. If three phase service or primary voltage service is supplied it shall <br />be under rates available for such service. <br />A <br />