Ms. Katie Larsen <br />06/03/2020 <br />Page 6 <br />a. Provide invert elevations, slope, material, and size of pipe. <br />b. Provide a construction detail for draintile installation. <br />c. How will the draintile be constructed over/under the trench drain for the parking <br />lot? They are shown as overlapping on sheet C1.40 <br />d. Show linework for draintile on Storm Sewer Utility Sheet so it can be compared <br />with other storm system management design factors. <br />19. TANK AND TRENCH DRAINTILE SYSTEM: <br />a. Provide updated calculation and details regarding this system from previous <br />comments. <br />b. Show invert elevations, slope, material, and size of pipe on utility plan <br />c. Systems are not allowed to flow into the sanitary in the underground parking <br />during any design event or situation. Install a valve to protect the sanitary sewer <br />system in the parking garage. <br />• Water Supply <br />The proposed site is currently not served by municipal water and on site wells shall be abandoned per <br />MDH. This area of the City, Woodridge Estates, is currently a low pressure area. The City's <br />Comprehensive Plan and water system model identifies the need for a 12-inch diameter trunk <br />watermain to be looped through the Lyngblomsten development site to serve the fire flow needs for <br />the site, and to improve flow within this area of Lino Lakes. The Lyngblomsten site will also have an 8- <br />inch diameter watermain and service lines throughout the site. <br />Comments: <br />The applicant shall provide profile views of the proposed watermain in the construction <br />plans. <br />Noted, profile plans will be provided in the final plat documents. <br />Staff will review watermain profiles once watermain layout comments have been <br />addressed and the profile views are updated. General profile comments include: <br />a. Applicant shall state pipe material in profile view label (i.e. X" DIP WATERMAIN <br />— X' ) <br />b. Applicant shall show the "8' MIN. COVER" note on all profiles views that show <br />watermain and proposed grade <br />c. Applicant shall review that all plan view limits match the profile view limits on the <br />profile sheets. See sheet C1.82C as an example. Profile view includes MH 4, but <br />plan view does not <br />d. Applicant shall indicate on the profile where insulation may be needed between <br />storm sewer crossings and the watermain <br />2. Hydrant spacing shall be 200-feet (linear) max. The applicant shall provide detail or a figure <br />of proposed hydrant spacing & coverage. <br />3. The applicant should include service lines to the proposed commercial in Outlot C. <br />Service lines have been provided on the utility plans. (AJA 2020-05.08) <br />Applicant to adjust location of proposed 8" gate valve so that it does not conflict with the <br />proposed storm sewer. <br />4. Provide more separation between water service to Lot 5 and the storm sewer crossing. <br />5. Extend lead for Hydrant 6 or relocate Hydrant 6. Hydrant is currently within the paved <br />entrance. <br />6. Please review storm sewer and watermain layout near MH 112. It appears that there <br />may be layout conflicts. <br />Lyngblomsten Preliminary Plat Engineering Review <br />