Laserfiche WebLink
John Powell <br />January 23, 2001 <br />ID Page 2 <br />16. All watermain is to be listed as Ductile Iron Pipe Class 52. <br />17. The flow arrows for the sanitary sewer from Retail D to SSMH104 are pointing in the <br />wrong direction. <br />18. Storm sewer manhole STMH54 is labeled as STMH69 in the storm sewer table. <br />19. Storm sewer information including pipe size, lengths and grades must be shown in the <br />plan view. <br />20. The flow arrows from CB55 to STMH54 are pointing in the wrong direction. <br />21. The flow arrows from F 1 to CBMH 19 are pointing in the wrong direction. <br />22. The 894 contour around Pond 1 and the bioretension basin is drawn incorrectly. <br />23. Why do the storm sewer manholes and catch basins to have 3 -foot sumps? <br />24. Additional calculations are needed to support the bioretension basins. <br />If you have any questions or comments regarding this review, please contact me. <br />• <br />