Laserfiche WebLink
JAN-23-01 04 :07 PM CASTLE COS. INC. 651 702 9364 P. 03 <br /> 2912 Pentagon,Plan Review <br /> January 18,2001 <br /> Page 2 of 2 <br /> 9. At least one of the showers in both locker rooms trust comply with the requirements of MSBC Chapter 1341.0458. <br /> 10. Provide exit signs per UBC Section 1003.2.8.2, note that the maximum distance between,signs is 100 feet. It looks <br /> like you will need one additional at the junction'of areas 126;108 and 109. <br /> 11. What is your proposed plan for emergency lighting per UBC Section 1003.2.9? Note that all areas must be <br /> covered. <br /> 12. The rest room in the child care room must also,comply with all of the requirements in M SBC Chapter 1341 for <br /> handicap accessibility, clear floor space, grab bars, fixtures, etc. <br /> 13. The counter heights in the juice bar area must comply with the requirements of MSBC Chapter 1341.0520. <br /> 14. Maintain a minimum of 44"clear aisle width to the exit door in the cardio area. <br /> End of Comments <br /> Please respond to these comments by way of addendum.and/or revised plans as necessary. <br /> Respec submitted, <br /> Grego A. Schmit, C.B.O., Building Official/City of St. Anthony <br />