Laserfiche WebLink
MPJohnson * <br />Controls <br />HVAC and Controls Replacement <br />Roof Top Unit Replacement: The five (5) roof top DX <br />cooling units at City Hall are 12 years old and are nearing the <br />end of their recommended service life. Over the last several <br />years, service calls have been placed because the compressors <br />have been tripping out (shutting off) and there are holes in the <br />condensers which reduce the efficiency of the system. The <br />ASHRAE standard for light commercial roof top units shows a life expectancy of 12 -15 years. <br />While evaluating the existing units several options were investigated. Many of the current issues with <br />the units are based on low air flow and high cooling capacity. Some of these issues can be resolved <br />by combining units for proper air flow with capacity. Combining units No. 2 & 5 (Multipurpose <br />Room and Police Station) will provide better control and reliability for the building. Four (4) new <br />DX units will be installed on the roof in the same location as the existing units. New ductwork will <br />be installed on the roof as required for proper installation <br />Control Replacement: City Hall has an old pneumatic control system with an independent electronic <br />system for the roof top units. During the analysis, it was determined savings could be achieved by <br />equipment scheduling for better control of the building. The building automation system would <br />utilize the building's Ethernet LAN system to centralize and network building control, allowing <br />facility personnel to monitor the buildings remotely. <br />For more information on the controls see section `Building Automation System Control <br />Enhancements" <br />Boiler Plant Replacement: The existing hot water boilers <br />at the City Hall are inefficient to operate and are reaching <br />the end of their useful life. The current boilers are small, <br />modular atmospheric combustion units installed with six <br />independent boilers that fire in series to provide adequate <br />heat to the system. Because of the way these boilers are <br />installed and designed, maintenance is an issue for the <br />middle boilers —many of the repairs require the removal of <br />at least one boiler. Additionally, these boilers can only be <br />"on" or "off'. The staging of the boilers provides some <br />flexibility of heat supply for the system, but are not able to <br />provide cooler water to the system. As the outdoor air <br />temperature increases, there is less of a demand needed for <br />heating the water. The current boilers do not allow sufficient staging during these warmer times. <br />a result, additional energy is used during the warmer portions of the heating season. <br />As <br />Four new high - efficiency boilers will be installed and tied into the existing heating hydronic system. <br />These new boilers will be vented directly to the outside for combustion air, and provide the <br />appropriate water temperature that is needed for the spaces. The boilers will come with internal <br />controls that optimize efficiencies based on the outdoor air temperature. The new boilers will run in <br />unison to generate the water temperature required by the space. As a system, the boilers will be able <br />savings. <br />to have a high turn down to minimum output and step up to the maximum output resulting in energy <br />Page 12 City of St. Anthony Village <br />W <br />Performance Contract Analysis <br />NOT TO BE REPRODUCED OR DISTRIBUTED HOUT JOHNSON CONTROLS' PERMISSION <br />