Effective April 28, 2015 Chapter Four Subsurface Sewage Treatment System Regulations <br />(8) Perforated laterals must not be installed closer than 12 inches from the edges of the absorption bed <br />and perforated laterals must terminate no closer than 12 inches from the ends of the absorption bed. <br />(9) Pressure distribution ceanouts must be provided to check the system for proper operation and <br />cleaning of plugged perforations. Cleanouts must be accessible from final grade. <br />(10) Existing systems with gravity distribution which are retrofitted with an advanced treatment device <br />meeting treatment level A or B in Minnesota Rules 7083.4030, must monitor the system to <br />determine the presence of even distribution over the absorption area. If even distribution is not <br />occurring, pressure distribution must be employed. <br />Table IV — Maximum Number of Perforations Per Lateral <br />1/4-Inch Holes <br />Perforation <br />Pipe Diameter (Inches) <br />Spacing <br />1 <br />11/4 <br />1 %2 <br />2 &3 <br />2.0 <br />10 <br />13 <br />18 <br />30 60 <br />2.5 <br />8 <br />12 <br />16 <br />28 54 <br />3.0 <br />8 <br />12 <br />16 <br />25 52 <br />7/32-Inch <br />Holes <br />Perforation <br />Pi e Diameter (Inches) <br />Spacing <br />1 <br />11/4 <br />1'/2 <br />21OU <br />2.0 <br />11 <br />16 <br />21 <br />34 68 <br />2.5 <br />10 <br />14 <br />20 <br />32 64 <br />3.0 <br />9 <br />14 <br />19 <br />30 60 <br />3/16-Inch Holes <br />Perforation <br />Pi <br />e Diameter (Inches) <br />Spacing <br />1 <br />11/4 <br />1'/2 <br />2 <br />3 <br />2.0 <br />12 <br />18 <br />26 <br />46 <br />87 <br />2.5 <br />12 <br />17 <br />24 <br />40 <br />80 <br />3.0 <br />12 <br />16 <br />22 <br />37 <br />75 <br />1/8-Inch <br />Holes <br />Perforation <br />Pi <br />e Diameter (Inches) <br />Spacing <br />1 <br />11/4 <br />1'/z <br />2 <br />3 <br />2.0 <br />21 <br />33 <br />44 <br />74 <br />149 <br />2.5 <br />20 <br />30 <br />41 <br />69 <br />135 <br />3.0 <br />20 <br />29 <br />38 <br />64 <br />128 <br />14.5 Distribution of Effluent for MSTS. <br />For MSTS, distribution of effluent into a soil treatment and dispersal area must comply with all parts of Section 14, <br />or be designed by a registered professional engineer and approved by the Department. <br />14.6 Pressure Distribution Required for MSTS <br />MSTS must employ pressure distribution except as allowed under Section 14.4(10). <br />14.7 MSTS Zones Required <br />The distribution system for MSTS must be designed to dose and rest zones in accordance with operational <br />requirements. <br />57 Washington County Development Code <br />