Name: Corrin Wendell <br />Date: October 7, 2022 <br />Page: 6 <br /> <br />H:\Heidi\Planning\Planning Cases\1415 - Lennar - Final Plat 1st addition Variance Rezoning - Paul Tabone\City Engineer Comments Review Memo 10.6.docx <br /> <br />• Sheet CU-101: remove gate valves on Street 1.. show as ‘future’ gate valves when the stubs get <br />connected to. In the interim, stubs will need a corporation stop and 1” line extended to the <br />surface for flushing. The lines will need to be removed after successful pressure and bacteria <br />testing and flushing. In future additions, the plugs will be removed and a new gate valve will be <br />installed. Include gate valve on southern side of the tee to accommodate future connections <br />and minimize water outages. Shift both sewer and water mains north ~2’ so future gate valves <br />are not in curblines. Apply this methodology to all watermain stubs and update valving <br />accordingly. <br />• General note: sewer services should be downstream of water services. <br />• General note: show hydrant valves in plan view as part of hydrant and valve assembly <br />• Sanitary sewer is 17’+ deep near Street 4. Include and detail sanitary sewer risers when service <br />depths are greater than 14’. <br />• General note: hydrant along Vanderbie should be offset 3’ from the sidewalk to ensure the <br />hydrant valve does not end up in the curb. There are locations where the hydrant is only 3’ <br />behind the curb which could cause problems. <br />• Sheet CU-104: move hydrant in northwest quadrant of Allen Ave intersection so that hydrant <br />lead and valve aren’t in conflict with the storm sewer structure <br />• Sheet CU-104: no connection elevation is shown at existing sanitary sewer manhole. As visually <br />depicted, an outside drop will be required. Show and detail this work accordingly, including <br />reconstruction of the manhole bench and invert. <br />• Sheet CU-104: no information provided for size, type, and method of connection to the existing <br />watermain. <br />• Sheet CU-104: sewer and water connections within Allen Ave will undermine existing large- <br />diameter storm sewer – especially the deeper sanitary sewer. My guess is that the contractor <br />will need to remove/salvage and reinstall the storm sewer. Please consider this and make any <br />plan adjustments as necessary so that it is considered in advance versus a construction issue. <br />• Sheet CU-104 / Street H: sanitary sewer services will be in conflict with watermain between <br />stations 16+00 and 16+80. Providing addition sanitary sewer depth should eliminate the <br />conflicts. <br />• Sheet CU-104 / Street H: extend hydrant to 5’ behind curb – currently only 2’ behind curb and <br />hydrant valve will be in curb. It is difficult to tell from the plans what the proposed wall height is <br />here. Additional frost protection may be needed around the hydrant to prevent frost <br />penetration through the wall. <br />• Sheet CU-104 / Street H: extend sewer so that services do not require bends – manhole directly <br />behind the curb should suffice. <br />• Sheet CU-105 / Street H: No design roadway profile shown in profile view. Please add. Profile <br />view missing many utility components as well. <br />• Sheet CU-105 / Street H: sanitary sewer services to conflict with the watermain at crossing <br />between stations 10+25 through 11+50.