Laserfiche WebLink
• <br />• <br />• <br />Mr. Michael Grochala <br />November 2, 2005 <br />Page 3 <br />5. Dimension, or call out with notes, the horizontal separation between the water main and sanitary <br />sewer lines. <br />Preliminary Detail Sheet (C1.04) <br />1. All manhole and catch basin details need to call out the usage of Infi- Shield or equal neoprene sealing <br />sleeves around the rings and casting. <br />2. The typical sidewalk section detail has a typo calling out sidewalk to be 6" wide. <br />Landscaping Plan <br />1. Trees cannot be planted in medians that are located above the StormTech storm sewer chambers. <br />Site Plan by Ankeny Kell <br />1. It is suggested that a walk be placed from each of the accessible parking loading aisles to the main <br />walk through the median area. This will provide an accessible route that will not force people out <br />into the parking lot and drive aisles to access the crosswalk to the main entrance. <br />Please call me at 651.765.2912 if you have questions. <br />Sincerely, <br />SHORT ELLIOTT HENDRICKSON INC. <br />Stefan T. Higgins, PE <br />Project Engineer <br />xAko \linoh030503 \ymca revicw \ymca revicw.doc <br />Short Elliott Hendrickson Inc., 1701 West Knapp Street, Suite B. Rice Lake, WI 54868 -1350 <br />SEH is an equal opportunity employer 1 www.sehinc.com 1 715.236.4000 1 715.234.4069 fax <br />