Laserfiche WebLink
• <br />Mr. Michael Grochala <br />April 24, 2006 <br />Page 2 <br />3. Proposed grading around Buildings 9 and 10 must be revised to incorporate an access route to Pond 3, <br />as stated previously. The proposed grading, as currently shown, will not allow vehicle access to <br />Pond 3. <br />4. The sidewalk between Buildings 13 and 14 has a slope that is 20% or greater. Slopes on sidewalks <br />cannot exceed 5 %. <br />5. The sidewalk at the southwest corner of Building 7 has a slope of 10 %. Slopes on sidewalks cannot <br />exceed 5 %. <br />6. The grading between Building 1 and CBMH 110, as shown, appears to be flat. The rim elevation of <br />CBMH 110 could be lowered to provide positive drainage from the sidewalk to the catch_basin. <br />7. It appears retaining walls will be required for some of the buildings fronting Village Drive, Town <br />Center Parkway, and Woods Edge Boulevard. <br />8. Two rows of silt fence should be installed along the existing wetland, as additional protection at the <br />base of the proposed slope. <br />9. Emergency overflows should be identified for interior drive aisles. Slope stabilization in these areas <br />may be required. <br />10. Erosion control blanket is required where storm sewer outlets intersect pond slopes. <br />• Preliminary Sanitary Sewer and Water Main Plan (Sheet C4.0) <br />• <br />1. Note 10 on the plan sheet indicates that hydrants are to be located 5 feet behind back of curb. City <br />standards require hydrants to be located 4 feet behind back of curb. <br />Gate valves should be shown where required on the plans (hydrants, wet taps, etc.). <br />3. Show all water service lines coming off of Woods Edge Boulevard as beginning at the right -of -way <br />line. Stubs will be provided "by others" to the right -of -way line. <br />4. The hydrant leads between Buildings 11 and 12 and Buildings 13 and 14 shall be 6 -inch diameter <br />rather than the 8 -inch diameter as shown. All hydrant leads shall have 6 -inch diameter pipe. <br />5. Sanitary manhole 2 and CBMH 209 are located too close together to be constructed as shown. <br />6. The size of the water line on the west side of Building 14 is not labeled. <br />7. The westerly invert elevation for sanitary manhole MH -B in Woods Edge Boulevard shall be revised <br />to match the elevation of the north -south invert. <br />8. Show the sanitary sewer services off of Woods Edge Boulevard as connecting to stubs "by others" at <br />the right -of -way line. <br />9. The applicant should flatten the pipe grade from sanitary MH -A to MH 9 to minimum grade and <br />should steepen the pipe grade from MH 9 to MH 10 to increase cleanout velocities in the dead end <br />run of pipe. Having the dead end run of pipe, with its lower flows, at a slope greater than minimum <br />will aid in keeping the pipe cleanout velocities higher. <br />TRECEVED <br />APR 2 5 2006 <br />CITY OF LINO LAKES <br />